In DASYLab, the PCI-DAS1000 counter module gives an error similar to the following:
"MCC-DAQ Error Message:
Possible reason - Invalid counter device
Data Logger -Counter Error
Fille-inc-MCC-HL-CIO8254-AddCounterComplete.h Line 119"
More Info
DASYLab 10.00.01 Driver DLL Demo 10.0.0 - dated Nov 29-2007
InstaCal-5.83 DAS1000 driver 5.83
Driver files cbul32.sys 3.37.01, cbulwdm.sys 1.38.01
The PCI-DAS1000 has six counter channels:
Channels 0, 1, and 2 are not available to the user; they are used by the A/D circuitry..
Channels 4, 5, and 6 are available to the user.
The customer needs to manually tell DASYLab to use counter # 4 as the first user counter.